Call Us For Free
0508 000052
TECHNICAL INFORMATION
Frame Designation [ID]
Frame Size [AF]
Rated Current - In [A]
Number of Poles - P [Nr]
Rated Operational Maximum Voltage - Ue in AC [V]
Rated Operational frequency Hz
Rated Operational Maximum Voltage - Ue in DC [V]
Rated Impulse Withstand Voltage - Uimp [kV]
Rated Insulation Voltage - Ui [V]
Utilization Catagory
Reference Temperature °C
Operating Temperature °C
Storage Temperature °C
Rated ultimate short-circuit breaking capacity in AC - Icu
220 / 240 AC [kA]
380 / 415V AC [kA]
440 / 460V AC [kA]
480 / 500V AC [kA]
600 / 690V AC [kA]
Rated service short-circuit breaking capacity in AC - Ics [% Icu]
Reference Standard IEC
Trip Unit Types
CSE1 CSE2 CSE3
125 250 400
16, 20, 25, 32, 40, 50, 63, 80, 100, 125 125, 160, 200, 250 250, 320, 350, 400
2 / 3 / 4 2 / 3 / 4 3 / 4
690 690 690
50 / 60 50 / 60 50 / 60
500V 500V 500V
8 8 8
1000 1000 1000
A A A
+45 +45 +45
-5 to +50 -5 to +50 -5 to +50
-30 to +70 -30 to +70 -30 to +70
M NN S M NN S SX M NN S
35 50 75 35 50 75 75 35 50 75
25 36 50 25 36 50 50 25 36 50
22 30 44 22 30 44 44 22 30 44
18 28 42 18 28 42 42 18 28 42
15 20 30 15 20 30 30 15 20 30
100 100 100 100 100 100 75 100 100 100
IEC 60947-2 IEC 60947-2 IEC 60947-2
FTM/FMU/ATM/FMTU/MTU/ETM/ETM-M/ETM-C/ETM-MC FTM/FMU/ATM/FMTU/MTU/ETM/ETM-M/ETM-C/ETM-MC FTM/FMU/ATM/FMTU/MTU/ETM/ETM-M/ETM-C/ETM-MC
RELEASE SETTINGS
Frame Size Current Rating FTM Release Settings FMU Release Settings
Thermal Settings Magnetic Settings Thermal Settings Magnetic Current Settings
(2P/ 3P/ 4P)
1 Pole (2P/ 3P/ 4P)
CSE1 16A Fixed at 1.0 In - 350 Adjustable
0.8, 0.9, 1.0 In
350
20A - 450 450
25A - 450 450
32A - 600 600
40A - 600 600
50A - 600 600
63A - - -
80A - - -
100A - - -
125 - - -
CSE2 125A Fixed at 1.0 In - Fixed at 10In Adjustable
0.8, 0.9, 1.0 In
Fixed at 10In
160A -
200A -
250A -
CSE3 250A Fixed at 1.0 In - Fixed at 10In Adjustable
0.8, 0.9, 1.0 In
Fixed at 10In
320A -
350A -
400A -
ORDERING INFORMATION
CSE2 SX 250 ATM 3P - 200A
Frame Size Breaking Capacity Icu at 415V AC
for 2P, 3P, 4P / 240V AC for 1 pole
Frame Ampere Trip Units Poles Connections Current Rating
Code Code Icu in kA Ics in % Icu Code Code Code Code Code
CSE1 L 18 100 125 FTM
FMU
FMTU
ATM
MTU
ETM
ETM-M
ETM-C
ETM-MC
2P / 3P / 4P Front
Connection
16A, 20A, 25A, 32A, 40A, 50A,
63A, 80A, 100A, 125A
M 25 100
NN 36 100
S 50 100
CSE2 L 18 100 250 FTM
FMU
ATM
MTU
ETM
ETM-M
ETM-C
ETM-MC
2P / 3P / 4P Front
Connection
125A, 160A, 200A, 250A
M 25 100
NN 36 100
S 50 100
SX 50 75
CSE3 L 18 100 400 FTM
FMU
ATM
MTU
ETM
ETM-M
ETM-C
ETM-MC
3P / 4P Front
Connection
250A, 320A, 350A, 400A
M 25 100
NN 36 100
S 50 100
Stocked Items
CSE1NN125ATM3P-100A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 125AF, 80A, 36kA, 3Pole
CSE1NN125ATM3P-125A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 125AF, 80A, 36kA, 3Pole
CSE1NN125ATM3P-63A MCCB Winbreak1, Adjustable Thermal Magnetic, 415VAC, 125AF, 63A, 36kA, 3Pole
CSE1NN125ATM3P-80A MCCB Winbreak1, Adjustable Thermal Magnetic, 415VAC, 125AF, 80A, 36kA, 3Pole
CSE2NN250ATM3P-160A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 250AF, 160A, 36kA, 3Pole
CSE2NN250ATM3P-200A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 250AF, 200A, 36kA, 3Pole
CSE2NN250ATM3P-250A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 250AF, 200A, 36kA, 3Pole
CSE2S250ATM3P-200A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 250AF, 200A, Icu 50kA, 3Pole
CSE2S250ATM3P-250A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 250AF, 250A, Icu 50kA, 3Pole
CSE3NN400ATM3P--400A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 400A, 36kA, 3Pole
CSE3NN400ATM3P-320A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 320A, 36kA, 3Pole
CSE3NN400ATM3P-350A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 350A, 36kA, 3Pole
CSE3S400ATM3P-320A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 320A, 50kA (Ics=100% Icu), 3Pole
CSE3S400ATM3P-350A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 350A, 50kA (Ics=100% Icu), 3Pole
CSE3S400ATM3P-400A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 400AF, 400A, 50kA (Ics=100% Icu), 3Pole
CSE4NN630ATM3P-500A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 630AF, 500A, 36kA (Ics=100% Icu), 3Pole
CSE4NN630ATM3P-630A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 630AF, 630A, 36kA (Ics=100% Icu), 3Pole
CSE4S630ATM3P-500A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 630AF, 500A, 50kA (Ics=100% Icu), 3Pole
CSE4S630ATM3P-630A MCCB Winbreak1, Adjustable Thermal Magnetic 415VAC, 630AF, 630A, 50kA (Ics=100% Icu), 3Pole
Stocked Accessories
CSET2033 Extended Terminal for 250AF, 3 Pole MCCB(Set of 3)
CSET2503-ST Extended Terminal for 250AF(ETP Copper with 5mm thickness), 3 Pole MCCB (Set of 3)
CSET3033 Extended Terminal for Winbreak1, 400AF, 3 Pole MCCB (Set of 3)
CSET4033-WB1 Extended Terminals for 500-630A WB1-4 Frame, 630AF, 3 Pole MCCB (Set of 3)
EHW1-125 Extended Rotary Handle for Winbreak1 MCCB (CSE1)
EHW1-250 Extended Rotary Handle for Winbreak1 MCCB (CSE2)
EHW1-400-630 Extended rotary handle for Winbreak1 MCCB (CSE3/CSE4)
Brand
Brand
Brand